Gas vs Air Pressure Switches on Industrial Burners: What Each One Proves

A “pressure switch fault” on an industrial burner is not a single diagnosis. A gas-pressure switch may be monitoring fuel pressure at a gas-train point, while an air-pressure device may be proving fan pressure, vacuum, or the pressure difference between two points. The devices can look similar and may even come from the same manufacturer, but their pressure connections and safety functions are not interchangeable.
Start with the exact switch model, the medium connected to it, where its pressure port or ports lead, and the point in the burner sequence at which its contact is expected to change. BAITE currently lists DUNGS LGW...A4 differential pressure switches and GW...A5 compact pressure switches among its burner accessories. Their published functions show why the model and connection arrangement need to be identified before a technician adjusts or replaces anything.
Why the Burner Sequence Changes the Meaning of a Pressure-Switch Fault
Burner controls use pressure-switch contacts as permissives or safety inputs, but each input has a specific job. Siemens LME39 documentation, for example, includes air-pressure supervision with a functional check during startup and operation, depending on parameterization. A burner can therefore have a running fan while the controller is still waiting for the required air-pressure condition.
A fuel-pressure switch answers a different question. If a low-gas-pressure input opens as firing rate increases, the useful evidence is the pressure actually available at that monitoring point under flow. Falling supply pressure, regulator or filter pressure loss, valve-train restriction, or an unsuitable setting can all affect the result. Replacing the switch before checking the pressure can leave the underlying system condition unidentified.
Read the pressure-switch indication together with the sequence state. An air-pressure failure during purge belongs to a different diagnostic path from a low-gas-pressure trip near high fire.
GW and LGW Pressure Switches Can Monitor Different Pressure Relationships
DUNGS describes the LGW...A4 family as adjustable pressure switches that can monitor overpressure, underpressure, or differential pressure. In differential service, the switch responds to the pressure relationship between two pressure chambers. The dial range alone therefore does not tell you what the device is proving; the connected ports determine the pressure relationship it sees.
The GW...A5 family is described as a compact adjustable pressure switch for monitoring pressure deviations and is designed for use with DUNGS multifunctional devices, double solenoid valves, safety valves, and regulators. BAITE also lists the GW...A6 family. Exact pressure ranges and switching differences vary by submodel, so the family name alone is not enough for replacement selection.
In practical terms, an air differential switch needs evidence from both sides of its sensing arrangement: the P+/P- connections, fan and damper state, and the actual differential pressure. A gas-pressure switch needs evidence from the gas-train point it monitors, including pressure under the operating condition that produces the trip. In either case, a contact state without the corresponding pressure measurement gives only part of the diagnosis.
The Dial Setting Is a Switching Reference, Not a Pressure Measurement
BAITE's DUNGS accessory pages describe the setting wheel as the reference or switching point. The setting is not a substitute for a manometer reading. It defines where the contact is intended to change state within the applicable device tolerance; it does not show the live pressure in the gas train or air circuit.
Datasheets also specify a switching difference. The pressure at which the contact changes in one direction and the pressure at which it changes back are therefore not necessarily identical. This matters with an intermittent fault near the switching threshold: a contact that opens and later resets may be following its designed switching characteristic rather than sticking.
Measure the actual pressure with suitable instruments at the approved test point. For a differential-pressure installation, verify the pressure relationship across the two connected points and inspect the sensing tubes or passages. A blocked tapping, leaking tube, reversed connection, or changed furnace pressure can alter what the switch sees even when the switch itself is mechanically sound.
Read the Fault Pattern Before Replacing the Switch
The most useful first observation is when the contact fails to reach or maintain the expected state. Record that condition before changing the setting, because the original trip point can help distinguish a sensing problem from a real air- or gas-pressure problem.
| Observed pattern | First checks | What to establish before replacing the switch |
|---|---|---|
| Fan starts, but ignition is not released and the controller indicates an air-pressure condition | Fan rotation, air inlet, damper position, sensing tubes/ports, actual air or differential pressure, furnace resistance | Whether the required pressure condition is actually present at the switch connections |
| Burner runs at low fire but trips on low gas pressure as load increases | Dynamic inlet pressure, regulator outlet pressure, filter or valve pressure loss, shared gas demand | Whether gas pressure really falls at the switch location under the failing load |
| Pressure-switch fault begins after tubing, wiring, gas-train, fan, or burner service | Compare the installed ports, tubes, wiring contacts, orientation, and component model with the approved documentation | Whether the serviced configuration still matches the intended sensing function |
| The switch changes state during a bench or manual pressure test, but the burner still faults | Installed pressure at the actual operating point, controller input state, wiring continuity, sequence timing | Whether the burner is creating and transmitting the required pressure condition in service |
If the symptom is specifically a fan-running/no-ignition condition, the existing pre-purge and interlock troubleshooting guide covers the wider startup sequence. If the burner loses flame or trips only as gas demand rises, the high-fire gas-pressure troubleshooting guide covers the broader gas-supply and combustion checks. Here, the narrower task is to establish what the pressure switch is actually monitoring before assigning the fault to the switch.
What Must Match When a Pressure Switch Is Replaced
A replacement pressure switch is not selected by connection size or visual similarity alone. It has to preserve the intended monitoring function and be suitable for the installed circuit.
- Exact function: gas-pressure, air-pressure, vacuum, overpressure, underpressure, or differential-pressure monitoring as required by the system.
- Medium compatibility: the exact device must be suitable for the gas, air, flue gas, or other medium connected to it.
- Setting range and switching behavior: the required operating point must fall within the applicable model range, with the documented switching difference and tolerance understood.
- Maximum operating pressure: the device must be suitable for the pressure that can be applied at the installation point.
- Pressure ports and mounting: the installed arrangement must preserve the intended P+/P- or single-point pressure reference and any manufacturer-specific mounting requirements.
- Electrical function: contact arrangement, ratings, wiring, and the burner's control logic must match the approved design.
BAITE's burner pressure-switch range includes several DUNGS and other pressure-switch families with different ranges and functions. For a replacement inquiry, provide the complete burner model, controller model, pressure-switch manufacturer and full model code, fuel, pressure connections, and original application setting rather than requesting only “a gas pressure switch” or “an air switch.”
Safety Boundary for Pressure-Switch Adjustment and Service
Pressure switches used in burner safety circuits should not be bypassed, permanently jumpered, or arbitrarily reset to a lower or higher value simply to keep the burner running. A trip may be the correct response to a real loss of combustion-air proof or an abnormal fuel-pressure condition.
DUNGS pressure-switch instructions state that work on the device is for specialist personnel and that application-specific settings are to follow the appliance or boiler manufacturer's instructions. For gas-connected work, the applicable instructions also require pressure and electrical energy to be isolated and the required leakage and function checks to be completed after service. These instructions apply to the relevant DUNGS devices; the installed burner and site procedure remain the authority for the complete system.
Discuss a Burner Pressure-Switch or Interlock Issue
For BAITE technical support or replacement selection, send the burner model, controller model, exact pressure-switch model, fuel, fault indication, sequence stage, pressure-port or tubing arrangement, available pressure readings, and any recent fan, gas-train, wiring, or commissioning changes. Contact BAITE with the burner and pressure-switch details.
Frequently Asked Questions
Can a gas pressure switch and an air pressure switch be interchanged if the pressure range looks similar?
Not on that basis alone. The monitoring function, permitted medium, pressure-port arrangement, operating-pressure limit, electrical contacts, approvals, mounting, and required switching behavior all have to suit the installed burner circuit.
Does hearing a pressure switch click mean the switch is good?
A click can show that the mechanical switching mechanism moved during that test, but it does not verify the actual pressure at the installed sensing point, the electrical contact under operating conditions, the tubing or pressure path, or the controller input. Diagnose the complete sensing circuit.
Why can the air pressure switch fail even though the burner fan is running?
Fan rotation alone does not guarantee the required pressure at the switch. Incorrect rotation, a blocked inlet, damper position, fan condition, furnace resistance, a blocked sensing port, leaking or reversed tubing, or a changed reference pressure can all affect the pressure signal seen by the switch.
Should a low-gas-pressure switch be adjusted if it trips only at high fire?
First measure the gas pressure at the relevant test point while the fault occurs and compare the result with the approved burner and gas-train requirements. A high-fire trip can be caused by real pressure loss under flow, so changing the switch setting before measuring the system can hide the condition that needs attention.
Technical References
- DUNGS LGW...A4 Pressure Switches — DUNGS Combustion Controls
- DUNGS GW...A5 Compact Pressure Switches — DUNGS Combustion Controls
- Gas Burner Controls LME39 — Data Sheet — Siemens